Our Market leading Purge and Pressurisation safety device ensures the safe operation of electrical machines and enclosures within Zone 1/21 and 2/22 hazardous areas. The unique attributes of this system provide numerous advantages over its competitors.
PP1214 is designed in accordance with IEC 60079-2:2014 Ed 6/ EN 60079-2:2007, ensuring a pressurised and leakage compensated enclosure. This creates a non-hazardous atmosphere inside the enclosure by keeping a positive differential pressure between the pressurised enclosure and atmospheric pressure to ensure that no potentially explosive gases enter the electrical equipment.
This type of protection consists of two main stages:
Purge Cycle:
Activated when the electrical machine is OFF prior to being switched ON. Clean air/inert gas is blown through the machine and monitored to ensure compliance with IEC 60079-2:2014 Ed 6/ EN 60079-2:2014.
Leakage Compensation and Pressurisation Cycle:
Once purge cycle is satisfactory the machine is considered non-hazardous and ready to be switched ON. A positive differential pressure to atmospheric has to be maintained. This is achieved by compensating for any air/inert gas leakages that the machine might have.
PP1214.1.1
Remote
Manual ball valve
* ATEX
PP1214.2.1
Local
Manual ball valve
* ATEX
PP1214.3.1
Remote
Automatic electrical solenoid valve
* ATEX
PP1214.4.1
Local
Automatic electrical solenoid valve
* ATEX
PP1214.1.2
Remote
Manual ball valve
** ATEX and IEXEC
PP1214.2.2
Local
Manual ball valve
** ATEX and IEXEC
PP1214.3.2
Remote
Automatic electrical solenoid valve
** ATEX and IEXEC
PP1214.4.2
Local
Automatic electrical solenoid valve
** ATEX and IEXEC
*Ex d e [ib] [pxb] IIB T4 Gb
Ex tb [pxb] [ib] IIIC T135°C Db
**Ex d e [ib] [pxb] IIC T4 Gb
Ex tb [pxb] [ib] IIIC T135°C Db